https://www.bryair.com/faq/adsorption-chiller/what-capacity-cooling-tower-will-be-required/
=
What capacity cooling tower will be required? | Bryair
BryairFAQAdsorption ChillerWhat capacity cooling tower will be required?

What capacity cooling tower will be required?

Since the chiller must reject the cooling load and also the hot water energy to the cooling tower, on average 34,000 BTU’s per cooling ton are rejected to the tower. This is normal for a hot water driven chiller.

  • Bry Air newsletter pahwa_logo
  • bryair_logo
  • DRI Logo
  • Delair Logo
  • Bry Air tds_logo
  • accentium logo
×

BryCare Support

    If you need technical assistance/support, click the button below:

    Technical Assistance and Support →

    For commercial assistance, enter your contact details to start a conversation without obligation

    ×
    Top