|
PART SIX BRY-AIR DEHUMIDIFIERS FOR PRODUCT DRYING
Product drying applications include two general types:
bulk drying and continuous drying. In bulk drying the material is loaded
into a compartment and the entire load is dried as a batch. With continuous
drying the wet material is continuously fed into a drying chamber and
material continuously leaves the chamber, dried to the desired moisture
level.
Drying potentials can be increased in two ways by:
- Raising the product temperature by exposing
it to heated air
- Physically removing moisture from the surrounding
air
The quantity of air needed for proper drying will vary
widely with either type of drying system. But the drying characteristics
and the approach to the problem are similar.
The Bry-Air Dehumidifier performs no miracles
extracting moisture from the product into the surrounding air. But by
maintaining the air at a lower moisture level, the Dehumidifier can increase
the drying potential and the drying rate. More important, it can remove
the variable of weather as a factor in a drying operation.
Heating is less expensive than
drying, so the obvious questions is: Where do Bry-Air Dehumidifiers apply?
In most drying processes, the released moisture goes into the air and
must be physically removed or diluted with outside air. However, without
a desiccant dehumidifier, the lowest possible moisture level in the chamber
will equal that of the outside make-up air. But in practical terms, the
moisture content of the air in the chamber will generally be somewhat
higher than that of the outside air.
When heat is used alone, the drying potential is limited by the specific
humidity of the outside air plus the safe temperature to which the product
can be raised. Generally, a proper drying potential can be established
with heat and outside air if the temperature can be raised to 140°F
or above. If the temperature can not be raised over 120°F, then a
Bry-Air Dehumidifier is the best solution. For temperatures in the 120°F
to 140°F range, the decision depends on the product characteristics
and the desired degree of dryness.
Drying
operations involve the removal of free moisture, hygroscopic moisture,
or a combination of both. Free moisture is water held on the surface or
between molecules of a substance. Free moisture occurs when actual liquid
water is used to mix or wash the product prior to drying. Hygroscopic
moisture is held within the material's cells. Hygroscopic moisture will
take up or dispel water in relation to the relative humidity of the air
mixture to which it is exposed. When in equilibrium with air at 100 percent
rh, the material will be hygroscopically saturated. Any hygroscopic material
containing free moisture must be hygroscopically saturated.
The removal of free water is a surface evaporation function and follows
the calculation shown in Appendix 3 of this manual. The surface water
temperature should be assumed to be the wet-bulb temperature of the surrounding
air mixture. Note that air velocity is critical the drying speed.
The removal of hygroscipic moisture depends on the relative humidity difference
between that of the products' equilibrium condition and that of the surrounding
air. Velocity of the air over the product has little or no bearing on
the drying speed.
The figure 1 shows a typical drying curve. The sudden change in drying
rate (at the critical point) denotes where the initial drying via removal
of free moisture ends and hygroscopic drying takes over. In other words,
the product has lost its free moisture, but is still hygroscopically saturated.
Each material has a different physical form that determines how
it holds or gives up moisture. Since many of the newer materials lack
published data on their drying rates, selecting appropriate air drying
equipment must be done experimentally. The net effective drying surface
and the hygroscopic properties cannot be determined in any other way.
Most drying problems are really a request for improving the speed or quality
of an existing drying operation. For example, before today's advanced
dehumidifying equipment was available, candy manufacturers could make
their product only in winter. In summer, attempts to manufacture candy
might often end with a moldy product. Now, to meet production demands,
the use of cooling equipment and a desiccant dehumidifier can imitate
winter conditions all year.
Solving a drying problem usually involves a rather simple analysis of
the drying cycle. If the analysis (that is, the test run) can occur during
weather conditions that consistently give the desired drying result, the
problem is simplified. Regardless, any test run will show the product's
characteristics and give clues for solving the problem.
The test run should be made under actual production operation to secure
information in either of the two following categories.
Bulk type drying system. Several trays in different locations
in the compartment should be weighted and identified before being placed
in the drying cabinet. They should be weighed at the start and at predetermined
intervals (usually hourly), subtracting the tray weight, and quickly returning
the tray to its original position after weighing. At the same time a wet-and
dry-bulb reading (average throughout the cabinet) and air velocity reading
over the product should be taken. Continue these procedures until the
product in satisfactorily dried; weight should be noted at this point.
The purpose is to establish a totally dry weight. Temperature should be
high enough to keep the rh in the surrounding air at 5 percent or less.
Continuous type drying system. Here one must remove material samples
at the start, finish, and at regular intervals along the drying tunnel.
Such test points should be accurately marked and related to the drying
time. Each sample should be weighed as soon as removed, then thoroughly
dried at elevated temperature and reweighed. The dry-bulb temperature,
wet-bulb temperature, and air velocity over the product should be determined
at each point of product supply as well as at the start and end of the
drying tunnel.
From this information the weight readings can be converted
into percent of moisture and plotted against drying time. Moisture content
should be expressed as a percentage of the product's bone dry weight,
not as a percent weight of the test sample. If both free and hygroscopic
water are removed from the sample, a characteristic curve will resemble
that shown in the figure 1.
SIZING THE DESICCANT DEHUMIDIFIER
Bulk type drying. On the characteristic curve,
indicate the wet-bulb and dew-point temperatures equivalent to the reading
taken during the test up to the critical point. From the critical point
to the curve's end, show the dry-bulb temperature and the rh. The hygroscopic
drying phase should be considered in making the first analysis (that is,
the drying curve).
Some
hygroscopic moisture (near the product's surface) is removed at the critical
point. So make two assumptions:
- The product is hygroscopically saturated at
this point.
- The product is substantially in equilibrium
with the final rh at the end of the test (when it reaches the desired
moisture content).
Thus, the average drying potential for this
part of the test is:
[(90+final rh)/ 2 ] minus average rh observed during the hygroscopic drying
portion of the test.
If our test took 12 hours and we want it to be complete in 8 hours, or
two-thirds the amount of time, then the hygroscopic portion of the test,
which took 9 hours, needs to be completed in 6 hours. Further, the product's
moisture level at the critical point minus the moisture remaining after
complete drying equals the total weight of water to be removed in 6 hours.
This amount can be converted into grains per minute:
Total hygroscopic water removed
in lbs x 116.6
Time in hrs
To accomplish this dryness faster, the drying potential must be increased
proportionately to the rate of test time vs. the desired time. But the
product's average moisture level will be unchanged. Therefore, the average
rh for drying is found by:
Average product rh - Required rh potential.
The average product rh combined with the average dry-bulb temperature
dictates the specific humidity that must be maintained and defines the
operating conditions for the Desiccant Dehumidifier.
The drying temperature should be as high as practical
(usually 10°F below the maximum allowable product temperature). 95°F
entering air is the highest recommended level (See Chart 1, Appendix
4). Thus if temperatures greater than 95°F are needed in the drying
chamber, the recirculating air should be cooled to 95°F or below.
Here the cost of the cooling coil, booster fan, and water used will be
offset by the gain in moisture removal capacity. (Reduced ratings for
inlet temperatures up to 115°F can be calculated. See your Bry-Air
representative for details.)
The Bry-Air Dehumidifier will handle a mixture of recirculated air (at
the average specific humidity already determined) and a minimum of 5 percent
outside air (refer to Typical Flow Diagram). This establishes the level
at which the dehumidifier must operate. From Chart I Appendix
4, the leaving moisture is determined. The difference between the
gr/lb. moisture level maintained in the dehumidifier and the same parameter
in the air leaving the dehumidifier is the pick-up factor. This figure
divided into the average required moisture removal in gr/min determines
the dehumidifier size in lb./min air capacity.
This unit capacity must be checked against the "free moisture"
requirement this way:
Total weight of free moisture (gr/min)
Dehumidifier air
capacity (lb/min)
Equals moisture pickup factor (gr/lb)
Refer to Chart 1, Appendix 4. Knowing the
desired drying temperature helps pinpoint the inlet where the necessary
moisture removal will occur. For example, if 42 gr/lb. must be removed
(the drying temperature is 95°F), then follow the 95°F curve to
the point where the difference between the inlet and outlet moisture is
42 gr/lb. Here the result is nearly 60 gr/lb.; that is where the leaving
moisture is approximately 18 gr/lb.
To be safe, use a condition approximately 5 gr/lb. Above that shown on
the curve and allow for 5 percent outside air. Then the needed dew-point
and wet-bulb temperature values can be established. Determine the vapor
pressure equivalent for the temperature using Appendix
3. The difference between these items estab-lishes the drying potential.
Then determine the average vapor pressure difference for the test run
from the same table using the test dew-point and wet-bulb readings. The
ratio of vapor pressure difference with the Bry-Air Desiccant Dehumidifier
over that measured during the test should equal or be greater than the
ratio of the drying time. (test vs. desired.)
Since air velocity also affects free moisture evaporation, drying can
be some what controlled by changing air velocity to as high a level as
possible without disturbing the product. Use a by-pass or fans within
the chamber to increase the total circulation in the drying air circuit
above the Bry-Air Dehumidifier's capacity.
For the test run, establish a velocity factor:
(1 + test velocity in ft/min)
230*
*An established constant.
Also establish a velocity factor for the actual design:
(1 + actual velocity in ft/min)
230
At any given vapor pressure difference, the evaporation will vary directly
according to the above factors.
Continuous drying. Since continuous drying
systems characteristically have open ends, they usually require a great
deal of additional outside or make-up air to make up for all the openings.
For efficiency, keep such openings as small as practically possible. A
minimum leakage equivalent to a 200 fpm velocity through the area should
be positively introduced into the system.
The typical flow pattern for a continuous drying operation, shown below,
has a separate circulating system for free moisture removal; the dehumidifier
discharge is directed through the hygroscopic moisture phase. This configuration
takes advantage of rapid circulation in the first space without carrying
the wetter air into the final drying space. Note the separate circulating
system for the free moisture removal stage. Dehumidifier discharge is
directed through the hygroscopic moisture phase. This arrangement allows
rapid circulation in the first space without carrying over moisture into
the final drying space.
Use the bulk drying method to establish the vapor pressure difference
to allow drying to proceed satisfactorily in the free moisture stage.
Keep the velocity and temperature as high as practical. Design specifications
will help establish the total circulation. The temperature plus necessary
vapor pressure difference will establish the specific humidity (in gr/lb),
that must be maintained.
Express the total product moisture removal in gr/min and add the moisture
load introduced by make-up air. This latter load derives from the difference
in specific humidity between the maximum design outdoor level and that
maintained in the compartment multiplied by the quantity of outdoor air
(in lb./min). The proportionate quantity of recirculated and outside air
also determines the specific humidity of the mixture- which typifies air
entering the Dehumidifier.
If the pre-cooling Bry-Air Desiccant Dehumidifier is used, the air temperature
leaving the coil determines the Dehumidi-fier operating level. Refer to
Appendix 4, Chart 1 to calculate the moisture
level leaving the Dehumidifier and determine the removal per pound value;
Total moisture removal load,(gr/min)
Moisture removed by Dehumidifier (gr/lb)
Equals Dehumidifier size lb/min air capacity
The next step is to check the performance of the Dehumidifier in the hygroscopic
drying section, measured in gr/min.
Dehumidifier performance (lb/min)
2
Plus moisture level of air leaving Dehumidifier
Equals average moisture content of air in this portion of the drying chamber
Use the curve in Appendix 4, Chart 2 to determine
the temperature of air leaving the Dehumidifier. The departing moisture
will have a cooling effect; to find the average temperature subtract 0.625°F
for each gr/lb. pickup.
Now that moisture content and temperature are known, the average rh needed
is easily determined from a psychrometric chart. Compare this figure with
the necessary rh to insure proper drying within the bulk type dehumidifier.
This comparison will reveal whether or not the dehumidifier has the capacity
to produce the desired drying rate.
Maintaining drying temperature. As already noted, water evaporation
is a cooling process. Approximately 1052 Btu are needed to evaporate one
pound of water. In other words, 6.65 gr/lb. represent 1 Btu or 1 gr/lb.
represents 0.625°F.
As a product is dried, it releases moisture. Without proper control, this
moisture can cool down the environment and result in an equilibrium condition
where the drying practically ceases. So to maintain drying temperatures,
heat must be supplied in an amount represented by the evaporation rate.
Also, heat can be lost by conduction through cabinet walls. Thus it may
be necessary to control the product to drying temperature (heat or cool
it), and heat the make-up air to maintain the optimal drying temperature.
The process of adsorption is an exchange of heat in a like amount in the
reverse direction. Thus, air heats as it passes through the desiccant
dehumidifier. Approximately 30 percent additional heat builds up in the
desiccant from the previous reactivation period, so the dehumidifier supplies
all the required heat for evaporation and an additional 30 percent for
other purposes. In some, instances that additional heat is required; in
other cases, cooling may be needed.
DEHUMIDIFIER CAPACITY CONTROL
Several methods provide dehumidifier control.
On/Off control of the dehumidifier. Humidistat or dew-point control
monitoring of space or return air is a method used where continuous process
air is not needed. Often the dehumidifier is installed as an independent
unit and is not tied into the make-up or outside air circulation system.
On/Off control of reactivation heaters and blower. This control
method applies to continuous process air flow situations. However, the
process air will have more variation in humidity than with other control
methods.
Modulation of reactivation inlet temperature. This strategy yields
reduced energy consumption and supplies the
minimum energy needed to maintain the process condition.
Modulation of reactivation inlet temperature and air volume. By modulating
the reactivation air volume and temperature at specific values, the reactivation
capability is increased and can be used over a wide range of operating
conditions. This method also compensates for reductions in adsorption
capacity.
Process face and bypass damper control. Here the moisture control
of leaving air is due to varying the volume of air that bypasses the dehumidifier.
However, a constant supply air volume must be maintained. This is the
best scanario for tight humidity control.
CONCLUSION
Information in this manual was prepared to help customers choose the most
effective hand efficient dehumidifiers. Please contact Bry-Air's dehumidifier
experts for additional assistance and for more detailed information about
physical characteristics and performance data relating to Bry-Air Dehumidifiers.
 |
|
Bry-Air produced systems that are
built to meet specific
customer needs. Many customers require heating,
cooling, air filtration, etc. in addition to air drying.
|
|