|
PART FOUR CALCULATING THE VARIOUS MOISTURE
LOADS
CALCULATING LOAD INTERMITTENT
OPENINGS FIXED OPENINGS
The following methods have been used successfully
to calculate vapor loads; replacing the extensive calculations and laboratory
tests that might otherwise be required when a designer considers a new
space humidity problem or application.
Actual data from moisture loads entering a space through walls, floors,
and ceiling are available for various moisture loads and classes of construction.
A survey sheet, such as the sample in Appendix
2, will help you gather data for the needed calculations.
For standard types of construction, Bry-Air has determined
values for calculating the moisture load entering a space at controlled
humidity levels. Usually these calculations are relatively easy. The following
tables are aids for load calculations.
Outside humidity levels shown in the Table 1 are deliberately
higher than data for design specifications. This compensates for days
when the design wet-bulb temperatures are reached and the design dry-bulb
temperatures are lower than expected (thus creating higher total humidity).
Use the area design wet-bulb and the specific humidity figures shown here
to accurately rate the moisture control situation. Further information
on design can be found in Appendix 1 and in the ASHRAE Fundamentals Handbook,
"Weather Data and Design Considerations"
TABLE
I
Recommended Design Outside Moisture Level
|
DESIGN
|
DESIGN
|
|
OUTSIDE
WET BULB
|
SPECIFIC
HUMIDITY
|
OUTSIDE
WET BULB
|
SPECIFIC
HUMIDITY
|
|
°F
81
80
79
78
77
76
|
gr/lb
149
143
139
134
130
125
|
°F
75
74
73
72
71
70
|
gr/lb
121
117
113
109
106
102
|
|
TABLE
II
F1 Factor for Grain Difference
|
Gr/lb Difference
|
F1 Factor
|
35
40
50
60
70
80
90
100
110
120 |
1.0
1.12
1.35
1.59
1.82
2.06
2.29
2.53
2.76
3.00 |
|
TABLE III
F2 Factor for Space Permeation
Space moisture load is a combination
of permeation and infiltration and both will be encountered in determining
the load. Permeation is a straight line function of the difference in
interior and exterior vapor pressure (determined by gr/lb). As shown in
Table III, infiltration, represented in air changes per hour is not straight
line because of the two factors involved:
1. Each pound of air entering the space
will impose a moisture load determined by the difference in interior and
exterior moisture content.
2. Since the vapor pressure differs as the moisture content, the vapor
will move at a higher velocity than the air.
The combination of the two factors, results
in the space moisture load increasing at an ever increasing rate as the
difference between the interior and exterior moisture contents increase.
In view of the above, the F-1 factor is
used to adjust for the increased vapor velocity. Therefore, the combination
of the F-1, and F-2 factors represent the space moisture load anticipated
from both permeation and infiltration.
F3
Factors for Construction
Masonry or Frame Construction
Sheet metal, steel welded
Module panel, caulked & sealed |
1.00
0.30
0.50 |
|
F4
Factors for Vapor Barriers
Laminated, mylar (metallic
or polyethylene film)
Two layers edge sealed moisture paper
Two coats vapor proof paint |
0.50
0.67
0.75 |
|
Note: If the product of F3xF4 is less than 0.5, use
0.5. If the room is completely vapor proofed, with continuous vapor barrier
under the floor (or of all-metal, welded material) the factor may be reduced
to 0.3.
CALCULATING THE PERMEATING LOAD THROUGH A STRUCTURE
To determine the grains of moisture penetrating the construction
into a controlled space, use the following calculation.
V x G
x F1 x F2
x F3 x F4
C |
=
|
Grs/hr. (To
determine grains/minute divide answer by 60). |
| |
=
|
Amount of vapor able to permeate the
closed space through construction and vapor barriers. |
|
V
|
=
|
volume of controlled space in question
- ft.3 |
|
C
|
=
|
14 = constant used to translate ft.3
to pounds. This constant is used regardless of the density of the
air. |
 G
|
=
|
difference between the grs/lb of outside
air and the grs/lb desired in the controlled space. |
|
F1
|
=
|
moisture difference factor (Multiplier
from Table II). |
|
F2
|
=
|
Permeation factor (Multiplier from Table
III). |
|
F3
|
=
|
Construction factor - |
Table IV |
 |
See note with |
|
F4
|
=
|
Barrier Factor - |
Table IV |
Table IV. |
The above equation can be used to solve a typical example
as follows:
Problem : Find the amount of moisture that will permeate the room
defined below.
Sample Calculation - Space to be controlled:
(1) Room with 12'' masonry walls.
(2) Two coats of aluminum paint as vapor barrier.
(3) Volume of room - 22,000 cu.ft.3
(4) Outside Design: 95°F db 77°F wb (Table I Shows 130 gr/lb)
(5) Required - To hold in room - 40 gr/lb
V x G
x F1 x F2
x F3 x F4
C |
= Grains per hour. |
| V |
=
|
22,000 |
|
| C |
=
|
14 |
|
G |
=
|
130 - 40 = 90. |
Problem stipulates 40 gr/lb in the room;
therefore, 130 - 40 = 90. |
|
F1
|
=
|
2.29 From Table II |
(Factor for a moisture difference of
90 gr/lb). |
|
F2
|
=
|
0.58 From Table III |
locate 22,000 on bottom line. Travel
up and read curve at 0.58. |
|
F3
|
=
|
1.0 From Table IV. |
|
|
F4
|
=
|
.75 From Table IV |
(Factor for 2 coats of paint) |
|
22,000 x 90 x 2.29 x 0.58 x 1.0 x 0.75 =140,884
grs/hr
14
|
|
140,884 = 2348 grs/min
60
|
MOISTURE THROUGH INTERMITTENT OPENINGS
When such openings as service or personnel doors are opened
periodically, moisture-laden air can enter the conditioned space. Also,
vapor is constantly seeking drier space and will seep around and through
doors, even when they are closed.
Obviously the first precaution is to assure that openings
are adequately vapor-sealed. Then the drying equipment must deal with
the moisture load that comes into a controlled space when the door is
open. Assuming that the door is open only for short periods, calculate
the moisture load as follows:
| Ohr
|
=
|
A x G
x F1 = Grains
C |
| Ohr |
=
|
number of times each hour the door is
opened. (If unknown assume personnel door to be opened 2 times/hr
for every occupant.) |
| A |
=
|
area of the door opening in square feet. |
| C |
=
|
7 = constant |
G |
=
|
Difference in specific humidity in grs/lb
between controlled space and the adjacent space.
See Table I for outside wb to determine adjacent specific humidity.
|
| F1 |
=
|
factor from Table II for moisture difference. |
Example:
Door
area - 3' x 7'
Door
open - 6 times each hour
Moisture
difference - 90 grs/lb
Solution:
Ohr
x A x G
x F1 = grains per hour of additional load.
C
6 x 21 x 90 x 2.29 = 3710 grains
per hour added to controlled space.
7
Note: If the door is open for longer periods, use the calculation
scheme below.
MOISTURE THROUGH FIXED OPENINGS (CONVEYORS, OPEN
WINDOWS, ETC.)
To calculate the amount of moisture that travels through
a fixed opening from a wet space to a drier space, as follows:
A x 300
x G x F1
= Grains per hour of load through fixed opening.
C x D
Where
| A |
=
|
Area of fixed opening in
square feet, |
| 300 |
=
|
Experimental constant - velocity
of vapor, ft/hr, at 35 gr difference, |
| C |
=
|
14 = constant factor to translate ft.3
to pounds, |
| D |
=
|
feet = depth of opening, |
G |
=
|
grains = difference in grs/lb
between wet space and drier space. |
| F1 |
=
|
Moisture Difference Factor from Table
II. |
Example:
Conveyor
opening - 2 sq ft
Depth of opening - 1.5 sq ft
Moisture difference - 90 grains
Solution:
A
x 300 x G x
F1 = Grains
per hour
C
x D
2
x 300 x 90 x 2.29 = 5889 grains per hour
14 x 1.5
MOISTURE ORIGINATING IN THE CONTROLLED SPACE
Moisture or vapor originating in the controlled space
comes from any of several sources, depending on the intended use for the
space. Three basic sources of moisture are:
- Population load, including people and animals
- Product load, brought in by the product
- Process load
Population Load
People working in an area add moisture to the air because of breathing
and the evaporation of perspiration. When animals occupy the controlled
space, moisture release is contributed by their excrement.
How much moisture do people or animals add to a controlled
space? Such factors as the level of activity and the ambient temperature,
atmospheric pressure, and humidity are well documented. (see Appendix
3)
For animals, weigh the amount of water consumed during
a given period and assume that much water will be eliminated.
Product Load
Any material manufactured in a controlled area can bring moisture with
it and then release the moisture into the work area. Material brought
into a warehouse tends to become drier; it gives up moisture over a period
of time and loads the drying equipment accordingly.

A controlled, comfortable work environment is important to productivity.
|
All materials should be suspect. For
example, most metals bring very little moisture, but nonmetals can carry
surprisingly large amounts of water. The material's supplier should have
information on its moisture carrying characteristics.
If such data are unavailable, a simple
test should prevent an unexpected and substantial moisture load problem.
Place a sample of the material in a small, dry container, Or place some
material in a tall hopper and blow air over it to dry it. Measure the
moisture loss over an appropriate time interval to determine its dwell
time, or how fast it gives up moisture. In some cases, a small pilot plant
can be used to acquire definite data.
Process Load
The manufacturing process itself may expel moisture into the atmosphere
of a controlled space. Open tanks or trays of liquid will add to the moisture
load. (See Appendix 3.)
Other contributors include open stream exhausts, unvented combustion cycles,
and aging or curing cycles.
VENTILATING AIR-VAPOR LOAD (VAPOR BROUGHT IN WITH
OUTSIDE AIR)
Ventilating or make-up air from the outside contains moisture that must
be removed. Some designers add this moisture load to the total calculated
internal load to determine the required capacity of the drying equipment.
However, Bry-Air recommends this air not be considered
part of the internal load. Rather, it should be considered at its point
of entry.
If this added, or make-up air from outside mixes with
the return air and all go through the dehumidifier, then it is not added
to the internal moisture load. But if only part of this outside/return
air mixture passes through the dehumidifier, then the part bypassing the
dehumidifier must be added to the internal load of the room.
The added air is only part of the total air used in controlling space
humidity. Since it rarely gets into the controlled space without first
going through the dehumidifier, consider it at its point of entry-at the
dehumidifier.
Among the normal elements of an air drying system,
the air entering the drying equipment is a mixture of return air from
the controlled and make-up air from the outside. The temperature and moisture
content of this mixture depend on its two contributing streams.
|
Moisture-laden air enters through the process
inlet and moves through the Brysorb PlusTM
desiccant media. The desiccant adsorbs the water vapor and the dehumidified
air is then delivered through the process outlet directly into the
controlled space or air stream. Then, as the desiccant media rotates
into the reactivation airstream, the hot air entering through the
reactivation inlet drives off the moisture and exhausts it into
the atmosphere. After reactivation the hot, dry desiccant rotates
back into the process airstream where a small portion of the process
air cools the desiccant so that it can begin the adsorption process
all over again.
|
 |
|