Frequently Asked
Questions
This note is intended to assist users, decision makers
and consultants, in addressing some of the more common questions
and concerns related to use of dehumidification:
SECTION
- A
--- ABOUT DEHUMIDIFICATION
Q1.What is Relative Humidity ?
Atmospheric air is a mixture of various gases and water vapour.
The invisible water vapour in the air is called humidity.
The amount of water that can be contained in a pound of air
depends upon ......
Temperature of the air
Pressure of the air
At a constant pressure, the warmer the air the more water
vapour it can retain. If air at a certain temperature has
absorbed all the moisture it can hold at that temperature,
it is said to be saturated.
The amount of water present, or the degree of saturation is
evaluated in terms of Relative Humidity or Saturation ratio.
Hence, Relative Humidity is the actual water content in %
of that of a saturated volume.
When air is 50% saturated, it contains only one half the
amount of water than it can contain at the same temperature
and pressure. As the relative humidity approaches 100%, the
air can take on less and less moisture and at 100% relative
humidity, that air cannot hold more water.
If air is saturated with water vapour at a given temperature,
a drop in the temperature will lead to condensation of water
in the form of droplets. The temperature at which moisture
condenses out is the dewpoint temperature.
Q2.How do you measure Relative
Humidity?
Relative Humidity is determined by means of wet bulb and dry
bulb thermometers. The dry bulb temperature is the temperature
of air as determined by a standard thermometer. The wet bulb
temperature is determined by tying a wet wick over the bulb
dipped in a reservoir containing distilled water. Airflow
around the wick causes the evaporation of moisture thus lowering
the temperature and producing a reading lower than that on
the dry bulb thermometer.
The comparison between the two readings gives us the measurement
of water vapour in the air.
1. The lesser the difference - the wetter the air.
2. The greater the difference - The dryer the air.
The readings can be plotted on a chart known as the psychrometric
chart from where the properties of air vapour mixture like
relative humidity, absolute humidity, dewpoint can be directly
determined.
Q3.How Humidity Effects Industry
?
Humidity is a constant threat to production efficiency and
product quality.
The damage which can be caused by excessive relative humidity
are principally:-
- corrosion of steel and metals
- deteriorated characteristics of hygroscopic material
- increased harmful activity of micro organisms.
Q4.What are the typical methods
of dehumidification?
Principally there are three methods of dehumidification:-
... Over compression
... Refrigeration Dehumidification
... Sorption Dehumidification
Q5.How
can Compression be used to Dry Air?
Air compression suggests a method of reducing moisture content
in air. As air is compressed, partial pressure of the water
vapour in the water gas mixture rises to the point where moisture
can be condensed from the air at a higher temperature. This
approach is some times quite practical for very small volumes
of air but the cost of compressed air equipment, BHP requirement
and the amount of cooling water required for after-cooling
makes it very impractical for large volumes of air.
Q6.How
can Refrigeration be used to Dry Air?
Another method most commonly employed is the reduction of
moisture in the air by means of reducing the temperature.
By examination of the dew point alone or saturation curve
on the psychrometric chart. It can readily be seen that as
the temperature of the air is lowered, the amount of moisture
it can hold is reduced considerably. Thus by cooling the air
below the dew point, the moisture contained in that air can
be condensed out and some of the moisture vapour removed in
liquid form, but cooling to very low temperature makes the
refrigeration process impractical, as it requires a great
deal of subsequent re-heating. The reduction in air temperature
is also limited by the freezing point of water condensing
on the cooling coil, which in some designs is offset by complicated
brine spray and liquid lithium chloride type systems available
using a combination of refrigeration and adsorbent liquid.
These are very bulky and involve complicated control systems
for the proper maintenance of solution density.
Q7.How can Sorbents be used to
Dry Air?
Sorbents are solid or liquid materials which have the property
of extracting and holding other substances (usually water
vapour) brought into contact with them.
Sorbents can be classified into two general categories.
* Absorbents
* Adsorbents
Absorbent : A sorbent which changes either physically,
chemically or both during the sorption process.
Lithium Chloride is an example of solid absorbent. When water
is absorbed on this material it changes to hydrated state.
In liquid sorption dehumidification system, the air is passed
through sprays of a liquid sorbent such as lithium chloride
or glycol solution. The sorbent in an active state has a vapour
pressure below that of the air to be dehumidified and absorbs
moisture from the air stream. The sorbent solution during
the process of absorption becomes diluted with moisture which
during regeneration is given up to an air stream in which
the solution is heated.
Typically absorbent used is lithium chloride in either liquid
form or as solid crystals in a honey-comb shell.
Adsorbent : A sorbent which does not change physically
or chemically during the sorption process. Adsorbents are
normally granular beads or solids with porous structures making
it capable of holding large amounts of water on their surface.
The principle behind desiccant dehumidification is that the
desiccant is exposed to moisture laden air, from where it extract the moisture. The saturated desiccant
is heated, which drives off the collected moisture into the
exhaust air stream. The regenerated desiccant is ready for
use again. Thus a continuous cycle of sorption and regeneration
can be set up giving very low dew points. Typical absorbents
used are Silica gel, Molecular Sieve and Activated Alumina.
Thus it can be seen that chemical dehumidifiers based on
the principle of physical adsorption offer the most simple,
direct and economical method of humidity control.
SECTION
- B
---EQUIPMENT RELATED QUESTIONS
Q1.How does a Dehumidifier work?
The new range of Bry-Air Dehumidifiers are fluted media based
and remove moisture through a process of continuous "physical
adsorption".
The moisture is adsorbed in the dehumidification sector by
the fluted, metal silicate desiccant synthesized rotor and
is exhausted in the reactivation sector by a stream of hot
air in the counter flow. Following the reactivation process,
the adsorption sector is again ready to adsorb the moisture.
Thus, the two processes of "moisture adsorption"
and "reactivation" are taking place with separate
airflows continuously and simultaneously. Positive sealing
between chambers prevents mixing of the process and reactivation
air streams.
Q2.What is the range and capability of
Desiccant Dehumidifiers and to what level can relative humidity
(RH) be controlled by them ?
A. Bry-Air dehumidifiers incorporating desiccant synthesized
rotor are available in a range of 170 cmh (100 cfm) to 40,000
cmh (24,000 cfm) as standard and engineered/packaged systems
B. As the dehumidifiers use desiccants, they work independent
of apparatus dew point (ADP), and can continuously maintain
relative humidity as low as 1%, even at subzero temperatures.
Q3.Are the humidity levels, being specified,
not easily achievable with regular air conditioning or refrigeration?
Two items are significant in deciding the choice of the final
equipment :
i) The amount of latent (moisture) load in relation to the
total load.
ii) The relative humidity specified to be maintained
a) Generally, if the relative humidity is to be maintained
between 50-60%, it is more economical and preferred to employ
standard air conditioning. However, if the latent load, even
at this RH levels, is predominant or significant, e.g. Supermarkets,
large fresh air equipments, it is recommended and preferred
to divide the sensible load on the refrigeration equipment
and latent load on desiccant dehumidification equipment.
b) For relative humidity to be maintained below 45 to 50%,
desiccant dehumidifiers offer the most economical, efficient
and simplest method of humidity control.
c) Often humidity levels are not correctly specified as the
user is not aware as to what RH levels and moisture will have
ill-effect on its products and processes.
Q4.What are the limitations in controlling
RH with central air-conditioning plants/window air conditioners?
In tropical areas like India, with normal central air conditioning
plants, lowest relative humidity of 50%-60%, at best, are
attainable economically, at room temperatures between 20°C
to 24°C. This again is only possible with special design
of the cooling coil and appropriate selection of the apparatus
dew point and provision of sufficient reheat.
With window air-conditioners or split air-conditioning units, in the absence
of specially designed cooling coils and reheat provision,
typical relative humidity of 60-70% are commonly experienced
at times of high outside moisture ambient conditions like
monsoon.
Removal of large water vapour/moisture through cooling requires
after cooling to apparatus dew point close to freezing and
substantial subsequent reheating, thus requiring both over
sizing of the cooling equipment, as also increasing the operating
cost with higher BHP per ton consumed, and reheat energy.
Q5.How is the dehumidification equipment
sized?
To size the equipment, it is first necessary to correctly
estimate the moisture load. At low humidity, water vapour
will permeate at very significant rate and large quantity
based on vapour pressure difference. As ASHRAE has not laid
out moisture estimation procedures for low humidity requirements,
most air conditioning engineers are not fully equipped to
correctly estimate the moisture load. Estimation of the moisture
load procedure is explained in a very easy to understand manner
in the Bry-Air design
and engineering data manual.
Once the moisture load has been correctly estimated the sizing
of the dehumidifier is a relatively simpler task. Please see
Bry-Air engineering data manual or call our nearest office
for support.
Q6.Is there any quick thumb rule applicable
for determining the equipment selection ?
No, the moisture load in a particular area is directly influenced
by :
a) The volume of the room
b) Outside absolute humidity
c) Inside absolute humidity to be maintained
d) The vapour pressure resulting from the difference between
b) and c) above
e) The rate of migration of vapour resulting from d) above
i.e. vapour pressure difference
f) Conveyor openings, if any
g) Door size and door openings per hour
h) Number of people and their activity level
i) The fresh air quantity
All of these can significantly change the dehumidifier equipment
selection for the same size room.
Q7.Will the relative humidity
being maintained inside an environment, with the help of dehumidifier,
vary from season to season, depending upon the ambient temperature?
OR
What are the controls used to maintain
the desired RH, when there is a wide variation in ambient
temperatures and RH?
Like any refrigeration plant the load on the dehumidifier
system varies due to ambient conditions. The temperature control
is maintained by a thermostat. This RH control is achieved
with the help of humidistat or a proportionate RH controller.
There are several control option for optimizing dehumidifier
equipment energy/performance by one or more of many methods
like proportionate reactivation energy, switching on and off
the reactivation energy, switching off the dehumidifier, switching
off the rotary bed and the reactivation energy and keeping
the air flows on, etc.
Q8.Are higher size ducts required because
the latent heat has been removed from the supply air?
This is not necessary as duct size is calculated on the basis
of volume of air (measured in cfm). Any marginal increase
in cfm can be absorbed in the standard higher sized ducts
normally adopted.
Q9.Are there any specific recommendations
about building materials and paints to be used internally
to reduce humidity ingress, particularly in areas where low
humidity is to be maintained?
To prepare any space for humidity control, the choice of
vapour barrier is based on the degree of dryness or RH.
Commercial vapour barriers - moisture resistant construction
material, paints and other coating offer a variety of design
alternatives. Manufactures of vapour barrier materials can
supply specific information on their products.
Between 40 - 50% RH, special vapour barrier paints will provide
an economical reduction in moisture ingress. Below 35% RH,
it is recommended to prepare the conditioned space properly
with good vapour barrier treatment including polythene etc.
as an inside envelope for reducing the moisture load which
has a significant effect on the sizing of the equipment.
Q10.Is the equipment fire safe, specially
where inflammable or ignitable material is stored?
Dehumidifier equipment can be easily supplied with flameproof
motors and controls to make it suitable for hazardous areas
and flame proof/explosive proof applications. The Bry-Air
Dehumidifier incorporates inflammable, ECODRY metal silicate
desiccant synthesized rotor.
Q11.Are there any references/commendations
from users regarding the satisfactory usage of dehumidifiers?
Yes, references from
various users of Bry-Air dehumidifiers are available.
The fact that we have tens of thousands of Bry-Air Dehumidifiers
operating around the world and we are producing this product
in India and Malaysia in addition to USA and Brazil. The export
of the same to Middle East, various countries in American
continent and Europe, South East Asia, including Taiwan, Hong
Kong, Thailand, Indonesia, Singapore etc., China, African
continent including South Africa and West Asia, serves as
an adequate testimony of both the quality and capability of
Bry-Air Dehumidifiers.
Q12.What are the common maintenance
problems with dehumidifier? Are the spares and consumables
available easily?
Bry-Air dehumidifiers are easy to maintain and do not require
special skills either to operate or to maintain them. Elaborate
maintenance manuals provide easy to follow instructions for
installation, start-up and also a comprehensive trouble shooting
guide.
Consumables and spares are easily available through any of
the Representative, Regional or Branch offices located in
all major cities in India and abroad.
Bry-Air also offers training programmes for service technicians,
maintenance staff of user organisations, from time to time,
to familiarise them with the operation and maintenance of
the dehumidifier.
SECTION
- C
---APPLICATION RELATED QUESTIONS
Q1.What
are the common problems caused by moisture ?
Rust, mold, mildew, rot, decay, warping, stretching, lumping,
caking, agglomeration and decomposition are all common enough
problems encountered in our daily life. It is interesting
to note that the root cause of all these problems and many
more, is the presence of moisture or humidity in the air.
The storage, manufacture and transportation of material often
takes place in a humid environment which is not suited to
the moisture sensitivity of the material, leading to deterioration
of stored material, machinery, equipment and reduced product
appeal.
Humidity makes for mushy transfers in the printing industry
and irregular operation of packaging machines.
Seeds lose their germinating potential and dry fertilizers
agglomerate. In pumping stations and high voltage rooms, expensive
installations may rust as a result of unchecked condensation.
Q2.What
are the problems caused by moisture in the Pharmaceutical
Industry?
In the Pharmaceutical Industry, chemists have common problems
of decomposition and difficulty in compression of tablets
leading to breaking of tablets; lumping and caking of dry
powders, improper adhesion under pressure of tablets, improper
drying of gelatine capsules.
The presence of high humidity in the air is the cause of all
these problems.
The rapid advance in the discovery, manufacture and use of
modern drugs has focussed attention on an infinite number
of moisture control problems. Too much moisture in the air
may retard the growth of certain organic cultures. At the
very least, shelf life is particularly shortened by the presence
of humidity during the manufacturing process.
Q3.What are
the problems caused by moisture in the Food
Industry?
Potato chips, dry breakfast cereals and soda crackers exhibit
an affinity for water when exposed to high humid conditions
and will become soggy and unappetising.
In processing of powdery foods such as cocoas, gelatines,
the sticking or lumping of powder due to high humidity conditions
prevents its flow in the manufacturing process.
Q4.What
are the problems caused by moisture in the Electronic
Industry?
In the electronic industry, wirings on PCBs gets corroded
or short circuited due to presence of high humidity. Transistors
may break down or suffer a decrease in longevity and for wafer
production facilities the uniform growth of crystals is unachievable.
Q5.When packing products, we have a problem
with water condensing in the package. Is there a simple way
to avoid this?
This is common when packing cold products in a warmer environment,
where the relative humidity, i.e. moisture content, is too
high. This causes the moisture in the air to condense on the
product's cold surface.
1. Make sure the dew point of the air surrounding the product
is below surface temperature of the product by enveloping
the packaging equipment and dehumidified air into the envelope
or shroud.
Q6.When transporting powders, we have
persistent problems like sticking and caking. Why?
Powders are generally very hygroscopic, meaning they absorb
moisture easily. A preferred solution is to lower the relative
humidity in areas where the powder is processed and also if
conveying powders with air, dry the air to avoid absorption
of moisture by powder during conveying.
Q7.Will a Dehumidifier prevent mould
growth?
Yes. Mould growth appears on continually damp areas. A dehumidifier
will remove the moisture that is the root cause.
Q8.What
is Corrosion?
Corrosion is defined as destruction of a metal or alloy by
chemical or electrochemical reaction with its environment.
In most instances, the reaction is electrochemical in nature:
a flow of electricity between certain areas of a metal surface
through a solution capable of conducting an electric current.
This electrochemical action causes destructive alteration
(eating away) of a metal at areas.
Though corrosion is a complex function of many factors, the
three most important are-
- a voltage differential between pure and impure areas
- physical conditions of temperature and humidity
- and oxygen in the air.
Higher humidities may lead to higher condensation of water
on the metal surfaces. The concentration of molecules of water
vapour increases with increasing RH. This molecular thickness
of the layers of water eventually permits ionic conduction
which accelerates the rate of corrosion.
With iron or steel, the ferrous ion may react with hydroxyl
ion in water to form ferrous hydroxide and with oxygen to
produce ferric hydroxide (rust).
The rate of corrosion is faster where surfaces are exposed
to polluted air in combination with high relative humidity.
Industrial pollutants like sulphur dioxide enhance the corrosion
rate.
Corrosion or rusting of stored material can be seen in every
Industry-Defence, Marine, Precision parts etc.
|